Permit: T10CM01557

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM01557

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2010 ELECTRIC - FINAL Approved
08/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/27/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/26/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED REVISION APPROVED BY COT PLAN CHECK
2) LOCK NUT IN 600V DISCONNECT LOOSE
3) INSULATING BUSHING REQUIRED FOR CONDUIT TERMINATION #4 CONDUCTORS OR LARGER
4) VERIFY NEUTRAL BOND IN X-FORMER
5) SISMECS ON TRACK LIGHTING
6) OK TCO FOR STOCKING (ELECTRICAL)