Permit: T10CM01538

Parcel: 128120030


Addresses:

617 S JANET AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01538

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/24/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) LINE ITEMS 1, 2 AND 3 OK-RECALL FOR ITEMS#4-11
08/02/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ROOF STRUCTURE IS NOT STRONG ENOUGH TO SUPPORT THE WEIGHT OF THE NEW UNIT
2) CONTRACTOR ALSO CUT A 1" X 8" BRACE FROM 1 TRUSS
3) PROVIDE THE REQUIRED STRUCTUAL DRAWING FOR NEW UNIT ON ROOF. HAVE A STRUCTUAL ENGINEER REVIEW THE STRUCTURE
4) RELOCATE THE ELECTRICAL CONDUIT TO THE ROOF
5) REPAIR BIRD BLOCK BEHIND ELECTRIC MAST.
6) ID CIRCUIT BREAKER
7) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND-SUPPORT EVERY 4'
8) PAINT WITH LATEX PAINT
9) PROVIDE A BUSHING IN THE ELECTRIC DISCONNECT
10) PROVIDE THE REQUIRED SERVICE RECEPT ON THE ROOF, MUST BE GFI
11) PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING