Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01510
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONDUCTOR COLORS TO BE PER 210.5 AMENDMENTS 2) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 3) BOND RACEWAY PER 250.64 (E) 4) MAINTAIN WORKING CLEARANCES AT SWITCH BOARD 5) FINISH LABELING 690.17 |