Permit: T10CM01510

Parcel: 13204007A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01510

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONDUCTOR COLORS TO BE PER 210.5 AMENDMENTS
2) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
3) BOND RACEWAY PER 250.64 (E)
4) MAINTAIN WORKING CLEARANCES AT SWITCH BOARD
5) FINISH LABELING 690.17