Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONDUCTOR COLORS TO BE PER 210.5 AMENDMENTS 2) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 3) BOND RACEWAY PER 250.64 (E) 4) MAINTAIN WORKING CLEARANCES AT SWITCH BOARD 5) FINISH LABELING 690.17 |