Permit: T10CM01509

Parcel: 11717023D


Addresses:

88 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T10CM01509

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2011 ELECTRIC - UNDERGROUND Approved
12/30/2010 ELECTRIC - UNDERGROUND Partial Approval NEED TO RELOCATE OUTLETS AND CONDUITS IN BEAM LINE 15 FROM A-C. CANNOT HAVE PLASTIC IN CRUSH ZONES OF TENDONS. CONDUIT BURNING DECK AT J14 AND TOO CLOSE TO TOP OF SLAB AT I13.
11/08/2010 ELECTRIC - UNDERGROUND Partial Approval CONDUITS AND CABLES INSIDE COLS AND SHEARWALLS SE LEVEL B1 OK

CONDUITS AND CABLES INSIDE COLUMNS NW LEVEL 2 OK
10/19/2010 ELECTRIC - UNDERGROUND Partial Approval IN SLAB ENT AND BOXES OK FOR B2-SE AND PLAZA NW
09/29/2010 ELECTRIC - UNDERGROUND Partial Approval IN SLAB CONDUITS LEVEL B1 AREA 3-11/E-J OK
09/29/2010 ELECTRIC - UNDERGROUND Partial Approval OK TO CLOSE AND PLACE COLUMNS AND SHEAR WALLS LEVEL B1 @ E-J/3-11
09/24/2010 ELECTRIC - UNDERGROUND Partial Approval OK LEVEL B2 AREA A-E/3-11 FOR IN SLAB ELECTRICAL
09/01/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/23/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3/0 TO REBAR AND CADWELDS AS MARKED
2) OK PVC IN SLAB 1-4" AND 2-2 1/2"
3) GROUNDING ELECTRODE CONDUCTOR TO BE NEAR BOTTOM PER NEC REQUIREMENTS
08/19/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PVC: 4-2 1/2", 4-4", 3-1 1/2" AND 1-1"
2) OK PVC CONDUITS
3) TEMP SERVICE TO EDGE OF RETAINING WALL
4) STRUCTURE AT CENTER