Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T10CM01509
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2011 | ELECTRIC - UNDERGROUND | Approved | ||
12/30/2010 | ELECTRIC - UNDERGROUND | Partial Approval | NEED TO RELOCATE OUTLETS AND CONDUITS IN BEAM LINE 15 FROM A-C. CANNOT HAVE PLASTIC IN CRUSH ZONES OF TENDONS. CONDUIT BURNING DECK AT J14 AND TOO CLOSE TO TOP OF SLAB AT I13. | |
11/08/2010 | ELECTRIC - UNDERGROUND | Partial Approval | CONDUITS AND CABLES INSIDE COLS AND SHEARWALLS SE LEVEL B1 OK CONDUITS AND CABLES INSIDE COLUMNS NW LEVEL 2 OK |
|
10/19/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IN SLAB ENT AND BOXES OK FOR B2-SE AND PLAZA NW | |
09/29/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IN SLAB CONDUITS LEVEL B1 AREA 3-11/E-J OK | |
09/29/2010 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO CLOSE AND PLACE COLUMNS AND SHEAR WALLS LEVEL B1 @ E-J/3-11 | |
09/24/2010 | ELECTRIC - UNDERGROUND | Partial Approval | OK LEVEL B2 AREA A-E/3-11 FOR IN SLAB ELECTRICAL | |
09/01/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
08/23/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3/0 TO REBAR AND CADWELDS AS MARKED 2) OK PVC IN SLAB 1-4" AND 2-2 1/2" 3) GROUNDING ELECTRODE CONDUCTOR TO BE NEAR BOTTOM PER NEC REQUIREMENTS |
|
08/19/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PVC: 4-2 1/2", 4-4", 3-1 1/2" AND 1-1" 2) OK PVC CONDUITS 3) TEMP SERVICE TO EDGE OF RETAINING WALL 4) STRUCTURE AT CENTER |