Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T10CM01509
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2011 | ELECTRIC - UFER | Approved | ||
09/09/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) OK CADWELDS UP COLUMNS MARKED |
|
09/08/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) LOOKED AT BY LEE RAY |
|
09/07/2010 | ELECTRIC - UFER | Partial Approval | REMAINING CABLE AND CAD-WELDS LEVEL B-3 AREA 11.5-16 / A-E OK. | |
09/01/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) OK CADWELDS AS MARKED 2) OK PVC CONDUITS AS MARKED 3) OK CONNECTION TO REBAR |
|
08/31/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) OK CADWELD AS MARKED |
|
08/27/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) OK GROUNDING ELECTRODE RING AS MARKED 2) FINISH CADWELDS FOR LIGHTING |
|
08/23/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* | |
08/16/2010 | ELECTRIC - UFER | Partial Approval | AREA 3-11.7 / E-J OK 3/0 TO REBAR + CAD WEEDS AS MARKED ON PLANS OK PVC CONDUITS 2-1 1/4 + 2-1/" AS MARKED ON PLANS *THIS IS NOT A GROUND RING BUT A CONCRETE ENCASED ELETRODE RUN IN A RING PER RICK THE ENGINEER |