Permit: T10CM01509

Parcel: 11717023D


Addresses:

88 E BROADWAY BL


Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T10CM01509

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2011 STEM WALL/RETAINING WALL Approved
01/05/2011 STEM WALL/RETAINING WALL Partial Approval
12/30/2010 STEM WALL/RETAINING WALL Partial Approval COLS AND SHEAR WALLS SOUTH PLAZA LEVEL OK
12/09/2010 STEM WALL/RETAINING WALL Partial Approval SHEARWALLS NE LEVEL 5 OK TO PLACE
12/08/2010 STEM WALL/RETAINING WALL Partial Approval COLUMNS LEVEL 5 NE OK TO CLOSE AND PLACE
12/06/2010 STEM WALL/RETAINING WALL Partial Approval COLS LEVEL 4 NW OK TO PLACE
12/06/2010 STEM WALL/RETAINING WALL Partial Approval LEVEL 4 NW COLS AND SHEARWALLS OK
11/29/2010 STEM WALL/RETAINING WALL Partial Approval SHEARWALLS LEVEL 4 NE OK TO CLOSE
11/08/2010 STEM WALL/RETAINING WALL Partial Approval COLS & SHEARWALLS LEVEL B1 SE OK

COLS NW LEVEL 2 OK
11/01/2010 STEM WALL/RETAINING WALL Partial Approval COLUMNS AND SHEAR WALLS OK NW LEVEL B1
COLUMNS OK NE LEVEL 2
10/28/2010 STEM WALL/RETAINING WALL Partial Approval ALL LEVEL 1 COLUMNS AND SHEAR WALLS NORTH SIDE OK TO PLACE
10/28/2010 STEM WALL/RETAINING WALL Partial Approval COLS AT B2 - B1 RAMP OK
10/19/2010 STEM WALL/RETAINING WALL Partial Approval B2 LEVEL SW COLS OK TO PLACE
PLAZA LEVEL NE COLS & SHEARWALLS OK TO PLACE
10/18/2010 STEM WALL/RETAINING WALL Partial Approval OK TO CLOSE COLUMNS PLAZA LEVEL NE QUADRANT
10/13/2010 STEM WALL/RETAINING WALL Partial Approval PROGRESS ONLY. NOTHING READY TO PLACE
10/12/2010 STEM WALL/RETAINING WALL Partial Approval PROGRESS ONLY. NOTHING READY TO PLACE
10/05/2010 STEM WALL/RETAINING WALL Partial Approval COLUMNS AND SHEARWALLS LEVEL B1 A-E/3-11 OK
10/01/2010 STEM WALL/RETAINING WALL Partial Approval PLACEMENT OF COLS AND SHEARWALLS LEVEL B1 AREA E-J/3-11 OK.
09/29/2010 STEM WALL/RETAINING WALL Partial Approval OK TO CLOSE AND PLACE COLUMNS AND SHEAR WALLS LEVEL B1 @ E-J/3-11
09/27/2010 STEM WALL/RETAINING WALL Partial Approval COLUMNS AND STEMWALLS LEVEL B2 A-E/3-11
09/23/2010 STEM WALL/RETAINING WALL Partial Approval SHOTCRETE WALLS BASEMENT WALLS COMPLETE.

NEED TO CLEAN STEEL ON COLUMNS AT LEVEL B2 @ B7 AND E11
09/21/2010 STEM WALL/RETAINING WALL Partial Approval COMPLETION OF WALL LINE 16 OK.

OK TO PLACE LINE A / 11-16
09/20/2010 STEM WALL/RETAINING WALL Partial Approval OK TO CLOSE COLUMNS LEVEL B2 AREA E-J/3-11.

SHEARWALL NOT READY.
09/17/2010 STEM WALL/RETAINING WALL Partial Approval LINE 16 OK TO PLACE SHOTCRETE.
09/15/2010 STEM WALL/RETAINING WALL Partial Approval LINE 16 G-J OK TO PLACE SHOTCRETE

NEED TO ADDRESS GSN'S FOR C.I.P. CONCRETE KEYNOTE #11, LINE I LEVEL B2 MISSING CHAMFER
09/14/2010 STEM WALL/RETAINING WALL Partial Approval LINE 16 NOT READY FOR INSPECTION. SLAB BARS OUT OF PLACE
09/13/2010 STEM WALL/RETAINING WALL Partial Approval LEVEL B3 COLS AREA A-J / 11-16 OK TO CLOSE

LINE J / 11-16 OK TO SHOTCRETE
09/09/2010 STEM WALL/RETAINING WALL Partial Approval OK TO CLOSE ALL COLS AREA F-G/11-16

LINE A / 7-11 OK TO SHOTCRETE

LINE J / 11-16 REQUIRES MINOR ADJUSTMENTS TO STEEL BEFORE PLACING SHOTCRETE. MAY BE VERIFIED BY SP. INSP.
09/08/2010 STEM WALL/RETAINING WALL Partial Approval 1) SHOTCRETE OK LINE A/TO 7; MISSING GROUNDING CONDUCTOR EXTENSION AT COL 7, LEVEL 11; PLEASE INSTALL BEFORE MOVING FORWARD
2) COL AT 12/G IS INCORRECT NEED C22 NOT C27
3) REMAINING COLS LINE 4 AND LINE 5 OK TO PLACE
09/07/2010 STEM WALL/RETAINING WALL Partial Approval PROGRESS ON LINE 3 / A-E OK.

OK TO BEGIN LINE A / 3-6
09/02/2010 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) COLUMN POURS OK AREA 3-11
2) DO NOT CLOSE C-2 COLUMN AT B/4 58.11 NEED TO EXTEND LIGHTING PROTECTION TO TOP OF COLUMN
3) LINE A WALL STILL NOT READY FOR ?
4) PORTION OF SW8 STILL REQUIRES HOOKS 12" ON CENTER-OK TO CLOSE WHEN SPECIAL INSPECTION VERIFIED
08/31/2010 STEM WALL/RETAINING WALL Partial Approval 1) COLS PLACED TODAY AREA 3-11 OK
2) OK TO CLOSE AND PLACE SWC,SW7,SW8 (SW8 REQUIRES HOOKS AT ENDS)
3) OK TO COLSET AND PLACE REMAINING COLS, EXCEPT NEED ELECTRICAL EXTENSIONS OR TERMINATIONS AT 3 COLS BEFORE CLOSING
4) BASEMENT WALL LINE "A" NOT READY
08/30/2010 STEM WALL/RETAINING WALL Partial Approval 100' OF SHOTCRETE LINE J / 11.5 - 6 LEVELS B3 TO B1 INSTALLED. I STILL NEED VERIFICATION THAT 100' BETWEEN CONSTRUCTION JOINTS IS ACCEPTABLE.

7 COLUMNS PLACED. 7 COLS OK TO CLOSE. OK TO CLOSE SW7, SW8, SWC.
08/26/2010 STEM WALL/RETAINING WALL Partial Approval LEVEL B3-- SW 7,8 & G.4 OK TO PLACE
08/25/2010 STEM WALL/RETAINING WALL Partial Approval SHOTCRETE WALL LINE 3 / A-E IN PLACE. NEED TO CLARIFY DETAIL 013 FOR VERITICAL CONTROL JOINTS AND VERIFY EXTRA BARS (#5 X 7' LONG 36" OC) ALONG B2 FLOOR LINE.

TIES AT COLUMNS REQUIRE 1" SEPARATION FOR CONCRETE ENCASEMENT. PLEASE HAVE RFI'S TAPED INTO PLAN SET.

CLARIFY AMERIDRAIN PLACEMENT BEHIND RETAINING WALL (SHORING WALL) RATHER THAN BEHIND STRUCTURAL WALL.
08/24/2010 STEM WALL/RETAINING WALL Partial Approval PLACEMENT OF PERIMITER STEEL LINE 3/E-J AND LINE J/3-11.5 OK. NEED CLARIFICATION ON TYING COLS LINE J TO WALL.
08/16/2010 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*