Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/17/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1 - LABELING TO BE PER SECTION 690.17 2 - MAINTAIN WORKING CLEARANCES, SECTION 110.26 3 - PLEASE VERIFY INVERTER/MODULES LISTING & LABELING 4 - VERIFY #8 CONNECTION TO INVERTERS/MODULES |