Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2010 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 08/24/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1" PVC FROM LIFT CONTROLLER TO LIFT STATION |
|
| 08/23/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) SIZE EQUIPMENT GROUND ON FEEDER FROM 400A DISCONNECT TO 400A PANEL PER PLANS 2) BONDING JUMPERS ON SERVICE NIPPLE TO BE #4 |
|
| 07/21/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3/4 PVC FOR SUMP PUMP SUBJECT TO REVISION (NOT ON PLANS) |