Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2010 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 06/08/2010 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UFER GROUNDING ELECTRODE TO BE TAPED TO BOND BOTH METER PACKS 250 NEC 2) BONDING BUSHING OR BONDING LOCK NUT ON 2 1/2" TERM. INTO TERM CAN. 250.92 NEC 3) BUSHING REQUIRED AT 2" TERM. INTO GUTTERS 300.4 NEC |