Permit: T10CM01482

Parcel: 111073740

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/28/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
03/25/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
UNIT #101:
1) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX
2) DO NOT USE DUCT TAPE OUTDOORS
3) SEAL THE T-TOP WHERE LINE SET EXITS ONTO ROOF
4) PROVIDE A TRAP IN CONDENSATE DRAIN
5) MARK FOR COIL DATA PLATE
6) INSULATE SHEET METAL SLEEVE ON FAN COIL