Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T10CM01474
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2010 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
07/22/2010 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST CORRECT SUITE NUMBER 2) PROVIDE 1/4" PER FOOT SLOPE 3) INSTALL ABOVE SLAB TEST FITTINGS AS REQUIRED BY UPC 712 FOR TESTING SUCCESIVE SECTIONS 4) INSTALL FOAM WRAPS AT CONCRETE PENETRATIONS 5) KEEP OPEN DRAIN PIPING CAPPED TO PREVENT THE ESCAPE OF SEWER GASES OR INSTALL P TRAP AT TEMPORARY CONDENSATE CONNECTION |