Permit: T10CM01474

Parcel: 108193130


Addresses:

4582 N 1ST AV #170

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/01/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/30/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) EM LTG NOT WORKING IN BACK ROOM
2) HARD WIRE INSTA HOT. INSTALL DISC. SW. OR CKT BRKR. LOCK OUT
11/29/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PANELS NOT LABELED CORRECTLY, ALSO CKTS NOT LABELED ACCURATELY