Permit: T10CM01474

Parcel: 108193130


Addresses:

4582 N 1ST AV #170


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T10CM01474

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/30/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SUPER
09/28/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL UNUSED CONDUITS, CABLING, TO BE REMOVED/ABANDONED 725-800 NEC
2) OPEN J-BOXES AND EXPOSED SPLICES
3) M/C AND OR FLEX CONDUIT TO BE TIED UP OFF CEILING GRID
4) ALL CABLING IN USE TO BE SUPPORTED TO STRUCTURE USING LISTED STRAPS 725-800 NEC
08/20/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK SOFFITS IN OFFICES