Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM01474
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/30/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER |
|
09/28/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL UNUSED CONDUITS, CABLING, TO BE REMOVED/ABANDONED 725-800 NEC 2) OPEN J-BOXES AND EXPOSED SPLICES 3) M/C AND OR FLEX CONDUIT TO BE TIED UP OFF CEILING GRID 4) ALL CABLING IN USE TO BE SUPPORTED TO STRUCTURE USING LISTED STRAPS 725-800 NEC |
|
08/20/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK SOFFITS IN OFFICES |