Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T10CM01470
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2010 | FRAMING | Approved | IVRS - Inspection :* | |
07/08/2010 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FRAME IS PARTIALLED UNTIL MECH INTERMEDIATE IS APPROVED |
|
06/30/2010 | FRAMING | Partial Approval | IVRS - Inspection :* 1) ROOF NAILING OK ONLY |
|
06/29/2010 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL ELECTRICAL WORK 2) ALL PLATES IN CONTACT WITH CONCRETE SHALL BE TREATED 3) 1/2" BOLTS REQUIRED WITHIN 12" OF PLATES EDGE 4) H2.5'S MISSING FROM DBL TOP PLATE TO STUDS 5) WHERE ARE THE DRAINS FOR EXISITING LAUNDRY ?? |