Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2011 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* 1) OK TO BACKFILL 2) NEED GROUND RODS AND ADDRESSES |
|
| 09/02/2010 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONTRACTOR INSTALLED 2 METER PACK, PLAN SHOWS 1 METER ALL IN ONE SERVICE 2) PERMIT DOES NOT ADDRESS 2 UNITS 3) GROUNDING ELECTRODE SYSTEM TO BE EXPOSED AT SERVICE, ALSO IS REQUIRED AT BOTH UNITS PER 250.32 NEC |