Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10CM01431
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2011 | FIRE - FINAL | Approved | Approved 2/1/11 | |
01/28/2011 | FIRE - FINAL | Partial Approval | Partial approved 1/28/11 1.) Batteries defaulting 2.) All appliances including telephone lines have been tested and approved. All signals tramsmitted and received. 3.) Must continue with the fire watch as reqiured. |
|
01/19/2011 | FIRE - FINAL | Denied | Not approved 1/19/11 1.) Fire/safety inspection OK 1.) Need final approval for Fire Alarm System. 2.) All appliances tested and approved. 3.) Need to verify signals with monitoring company on both phone lines. |
|
12/29/2010 | FIRE - FINAL | Partial Approval | Partial approval 12/29/10 1.) Life/Safety CofO fire inspection OK 2.) Code requiers that two phone lines be provided to monitor Fire Alarm System 3.) TCO permitted providing that a "Fire Watch" be in place when the school is back in session 4.) Need documentation from State inspector that the "Exhaust Hood System" was tested and approved. 5.) OK for Temporary Cof O |