Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2011 | FIRE - FINAL | Approved | Approved 1/19/11 | |
| 12/29/2010 | FIRE - FINAL | Partial Approval | Partial approvel 12/29/10 1.) Life/Safety inspection OK 2.) Visuals and audios for Fire Alarm System tested and approved. 3.) Unable to recieve "ground fault" or "circut disruption" signal on Fire panel. 4.) Need additional smoke detector in rooms #155 and #152. (too far from wall) 5.) Code requires that two telephone line be provided for the monitoring of the Fire Alarm System. 5.) TCO has been permitted provided that a "Fire Watch" is in place when the school is back in session. 6.) Order to establish Fire watch was issued 7.) OK for temporary Cof O |