Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01428

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ALL ITEMS DATED 9/20/10 OK
2) PROVIDE BALANCE REPORT
09/20/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTORS MUST BE WIRED TOGETHER TO SHUT OFF ALL A/C FANS THAT ARE SHARING THE SAME RETURN PLENIUM
2) PROVIDE AUDIBLE AND VISIBLE ALARM IN A SUPERVISED LOCATION
3) CONDENSATE HOSE MUST TERMINATE WITH A FITTING
4) ALL DUCT SMOKE DETECTORS SHOULD BE IN THE RETURN DUCTS, NOT SUPPLY
5) SEE ENGINEER FOR DIRECTION