Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM01428
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL ITEMS DATED 9/20/10 OK 2) PROVIDE BALANCE REPORT |
|
09/20/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS MUST BE WIRED TOGETHER TO SHUT OFF ALL A/C FANS THAT ARE SHARING THE SAME RETURN PLENIUM 2) PROVIDE AUDIBLE AND VISIBLE ALARM IN A SUPERVISED LOCATION 3) CONDENSATE HOSE MUST TERMINATE WITH A FITTING 4) ALL DUCT SMOKE DETECTORS SHOULD BE IN THE RETURN DUCTS, NOT SUPPLY 5) SEE ENGINEER FOR DIRECTION |