Permit: T10CM01425

Parcel: 129041820


Addresses:

2008 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM01425

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/01/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) DISCONNECT TO BE LINE SIDE TO SERVICE CONDUCTORS
2) LOAD SIDE TO PV
3) RECEIVED CHECK #1767 FOR $165.00
08/18/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE WRITE UP FOR 2000 E. BROADWAY
2) PLANS CALL FOR LINE SIDE TAP-HAVE A MULTI-POLE LOAD SIDE TAP
3) VERIFY WIRE CAPACITY FOR TAP LUG-SIZE OF CONDUCTORS