Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND BUSHINGS FOR GROUNDING ELECTRODE CONDUCTOR TO BE 250.64 (E) 2) RACEWAY OVER FILLED 3) TERMINATE GROUNDING ELECTRODE TO CORRECT LABELED TERMINAL MINIMUM GEC #8 250.66, 690.47 4) RE-LABEL SERVICE METERS TO VERIFY ADDRESSING 5) NO MORE THAN 360 DEGREE IN CONDUIT RUN 6) PROVIDE PHYSICAL PROTECTION FOR CONDUCTOR AT MODULES 7) BOND MOUNTING RACKS |