Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/06/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* ADD SERVICE UPGRADE & RELOCATION TO PERMIT. APPLY TO TEP | |
| 07/19/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : COMPLETE 1 AND 2 FROM PREVIOUS INSPECTION EXISTING 100 AMP SERVICE IS OVERLOADED. HAVE A LICENSED ELECTRICIAN CALCULATE LOADS FOR BOTH HOUSES & REQUIRED ELECTRIC FOR PROPER SIZING OF REQUIRED SERVICE |
|
| 06/03/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE EQUIPMENT (MY OPINION YOU NEED A SERVICE UPGRADE) 100 MAIN BREAKER, IS NOT SEALED IN PLACE AND AT MAIN DISCONNECT. MAYBE DIFFERENT MANUFACTURER OLD AND LABEL IS MISSING 2) PANEL BEARD NEXT TO MAIN DISCONNECT HAS OVERSIZED BREAKERS AND UNDERSIZED WIRE 3) 100 BREAKER INSTALLED IN PANEL BOARD FOR NEW ADDITION, CANNOT DO THAT. I.D. 100 AMP BREAKER FOR MANUFACTURER, CUTLER HAMMER PANEL (LABEL ALL CIRCUITS) |