Permit: T10CM01399

Parcel: 107110620


Addresses:

3107 N GERONIMO AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/07/2011 BUILDING - FINAL Approved IVRS - Inspection :*
06/06/2011 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :* ADD SERVICE UPGRADE & RELOCATION TO PERMIT. APPLY TO TEP
07/19/2010 BUILDING - FINAL Denied IVRS - Inspection :
COMPLETE 1 AND 2 FROM PREVIOUS INSPECTION
EXISTING 100 AMP SERVICE IS OVERLOADED.
HAVE A LICENSED ELECTRICIAN CALCULATE LOADS FOR BOTH HOUSES & REQUIRED ELECTRIC FOR PROPER SIZING OF REQUIRED SERVICE
06/03/2010 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SERVICE EQUIPMENT (MY OPINION YOU NEED A SERVICE UPGRADE) 100 MAIN BREAKER, IS NOT SEALED IN PLACE AND AT MAIN DISCONNECT. MAYBE DIFFERENT MANUFACTURER OLD AND LABEL IS MISSING
2) PANEL BEARD NEXT TO MAIN DISCONNECT HAS OVERSIZED BREAKERS AND UNDERSIZED WIRE
3) 100 BREAKER INSTALLED IN PANEL BOARD FOR NEW ADDITION, CANNOT DO THAT. I.D. 100 AMP BREAKER FOR MANUFACTURER, CUTLER HAMMER PANEL (LABEL ALL CIRCUITS)