Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 06/21/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING SPACE IN FRONT OF INTERIOR 110.26 2) LABELING IS NEEDED PER 690.17 3) SUPPORT PV MODULE CONDUCTORS AND CONNECTORS UP OFF OF ROOF 4) PREVENT WATER FROM ENTERING RACE WAY 5) PROVIDE PHYSICAL PROTECTION FOR CONDUCTORS 6) PROVIDE ROOF ACCESS 7) NEED PLANS AND PERMIT ON SITE |