Permit: T10CM01378

Parcel: 137055220


Addresses:

1217 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01378

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/12/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WILL NEED ONE LINE DRAWING REVISED TO ACTUAL INSTALLATION OF EQUIPMENT BEFORE FINAL
08/11/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS 110.12
2) NEED ELECTRICIAN PRESENT TO OPEN LIVE EQUIPMENT AND SERVICE
3) FEEDERS TO ENTER SECTION SERVED 408.3
4) LIGHT FIXTURE SCHEDULE DOES NOT SHOW LAMP TYPE OF ENERGY LOADS
5) CHECK ABOVE TILE-VDV NEXT TIME
07/29/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND HARD LIDS-RECEIVED LETTER FROM ARCHITECT
07/01/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GET ELECTRICAL NOTES PAGE, CAN YOU USE MC, FLEX AND 1/2 EMT ?