Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01378
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/12/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WILL NEED ONE LINE DRAWING REVISED TO ACTUAL INSTALLATION OF EQUIPMENT BEFORE FINAL |
|
08/11/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS 110.12 2) NEED ELECTRICIAN PRESENT TO OPEN LIVE EQUIPMENT AND SERVICE 3) FEEDERS TO ENTER SECTION SERVED 408.3 4) LIGHT FIXTURE SCHEDULE DOES NOT SHOW LAMP TYPE OF ENERGY LOADS 5) CHECK ABOVE TILE-VDV NEXT TIME |
|
07/29/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND HARD LIDS-RECEIVED LETTER FROM ARCHITECT |
|
07/01/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GET ELECTRICAL NOTES PAGE, CAN YOU USE MC, FLEX AND 1/2 EMT ? |