Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT INSULATION OK, OK TO COVER DUCT |
|
| 08/23/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE CONDENSATE NEEDS TO TERMINATE AT AN APPROVED LOCATION 2) ALL PVC JOINTS TO HAVE PURPLE PRIMER 3) ALL PVC TO BE U.V. PROTECTED 4) PROVIDE SERVICE OUTLET WITHIN 25' OF R.T.U. 5) CONTRACTOR TO BE ON SITE TO VERIFY MINIMUM 2" DUCT LINER (PROVIDE ? TO OPEN DUCT) 6) PROVIDE FILTER ON O.S.A. 7) PROVIDE O.S.A. SETTING DOCUMENTATION |