Permit: T10CM01367

Parcel: 11941008A


Addresses:

1841 W AJO WY

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/31/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT INSULATION OK, OK TO COVER DUCT
08/23/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE CONDENSATE NEEDS TO TERMINATE AT AN APPROVED LOCATION
2) ALL PVC JOINTS TO HAVE PURPLE PRIMER
3) ALL PVC TO BE U.V. PROTECTED
4) PROVIDE SERVICE OUTLET WITHIN 25' OF R.T.U.
5) CONTRACTOR TO BE ON SITE TO VERIFY MINIMUM 2" DUCT LINER (PROVIDE ? TO OPEN DUCT)
6) PROVIDE FILTER ON O.S.A.
7) PROVIDE O.S.A. SETTING DOCUMENTATION