Permit: T10CM01356

Parcel: 141153030

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/19/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/07/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT USE PLASTIC BOXES WITH METAL RACEWAYS NEC 314.3
2) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS, NOTE 12 SHEET 1
3) GROUND PV PANELS PER INSTRUCTIONS AND PROVIDE PLANS
4) PROVIDE INSTRUCTIONS FOR INSTALL OF KVAR UNIT, IT'S DBL TAPED WITH DRYER BREAKER
5) STRAP SEAL TIGHT PER NEC 350
07/02/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
06/24/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL BREAKERS LISTED FOR USE IN GE SERVICE PANEL
2) PLAN CALLS FOR 40 AMP BREAKER AT SERVICE PANEL
3) INSTALLATION TO COMPLY WITH PLANS, NEED TO READ ALL NOTES AND INSTALL PROPER LABELING PER PLANS & NEC 690
4) GROUNDING ELECTRODE TO BE CONTINOUS TO INVERTER
5) CANNOT USE WHITE CONDUCTOR AS GROUND
6) BOND AROUND REDUCING WASHERS OR INSTALL PER INSTUCTIONS
7) STRAP EMT TO WITHIN 3' OF CONNECTIONS
8) OPEN CONDUCTORS THRU ATTIC IS NOT A RECOGNIZABLE WIRING METHOD PER NEC
9) ALL ROOF PENETRATIONS REQUIRE PROPER FLASHING
10) SIZE JUNCTION BOXES PROPERLY NEC 314.16
11) USE WEATHER PROOF CONNECTORS AT JUNCTION BOX ENTRIES
12) SEAL ALL OPENINGS ON JUNCTION BOXES
13) GROUND MODULES PER INSTRUCTIONS PROVIDED WITH GROUNDING SYSTEM BEING USED. PROVIDE COPY OF INSTRUCTIONS FOR INSPECTOR
14) TIGHTEN ALL FITTINGS
15) SYSTEM NOT TO BE ENERGIZED UNTIL ELECTRIC INSPECTION APPROVED