Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROOF BELL BOX GROUNDING WIRE NOT BONDED AROUND GREEN SCREW 3/4 PVC MISSING BLOCKING + STRAPING 3/4 EMT NO STRAPIN PIPE CONECTOR LOOSE 2. 3/4 EMT FROM INVERTOR TO ROOF PANELS HAS TO BE STRAPPED 3' FROM CONNECTOR 3/4 EMT FROM INVERTER TO METER LOOSE + NO STRAPPING 3. PHOTOVOLTAIC DISCONECT GROUND LUG LOOSE FROM DISCONNECT TO PANEL EMT CONNECTOR LOOSE ALSO STRAP 3' FROM CONECTORS 4. COULD NOT FIND PERMIT OR SOLAR PANEL PRINT TO FINISH INSPECTION LOOKED IN GARAGE |