11/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/05/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE DUCT SMOKE DETECTOR TEST X4 2) RETURNED FOR AFTER HOURS INSPECTION AND RECEIVED CHECK IN THE AMOUNT OF $165.00 WITH CHECK #18190 3) DUCT SMOKE DETECTOR TEST OK X4 AIR BALANCE REPORT OK |
|
11/04/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR TEST FAILED 2) PAINT PVC ON ROOF 3) IDENTIFY UNIT DATA PLATES |
|
11/02/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE FIRE DAMPERS ON S/A 2) PROVIDE MIN. 75 CFM AT RESTROOMS 3) AIR BALANCE TO BE REVIEWED BY ENGINEER 4) PROVIDE DUCT SMOKE DETECTOR TEST ON 7.5 TON UNITS (4) 5) WHERE IS RETURN AIR FOR STOCK ROOM 6) PROVIDE FIRE DAMPER FOR CEILING REGISTERS ABOVE RESTROOMS |
|
10/27/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEE KEY NOTE 6 2) PROVIDE BALANCE REPORTS FOR RESTROOMS |