Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM01334

Parcel: 11301146Y


Addresses:

3603 N CAMPBELL AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01334

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/05/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE DUCT SMOKE DETECTOR TEST X4
2) RETURNED FOR AFTER HOURS INSPECTION AND RECEIVED CHECK IN THE AMOUNT OF $165.00 WITH CHECK #18190
3) DUCT SMOKE DETECTOR TEST OK X4 AIR BALANCE REPORT OK
11/04/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) DUCT SMOKE DETECTOR TEST FAILED
2) PAINT PVC ON ROOF
3) IDENTIFY UNIT DATA PLATES
11/02/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE FIRE DAMPERS ON S/A
2) PROVIDE MIN. 75 CFM AT RESTROOMS
3) AIR BALANCE TO BE REVIEWED BY ENGINEER
4) PROVIDE DUCT SMOKE DETECTOR TEST ON 7.5 TON UNITS (4)
5) WHERE IS RETURN AIR FOR STOCK ROOM
6) PROVIDE FIRE DAMPER FOR CEILING REGISTERS ABOVE RESTROOMS
10/27/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE KEY NOTE 6
2) PROVIDE BALANCE REPORTS FOR RESTROOMS