Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/18/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE MIN R-8 (2") DUCT LINE ON ALL ROOP TOP DUCT. 2. PROVIDE SAFETY RAIL AT ALL EQUIPM WITHIN 10' OF ROOF EDGE. TOTAL HEIGHT 42" EXTEND 19" BEYOND EQUIP. EDGES. CAN NOT PASS 21" SPHERE BETWEEN RAILS. |