Permit: T10CM01302

Parcel: 12810082B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01302

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) ALL CORRECTIONS HAVE BEEN MADE
2) AIR BALANCE OK
3) DUCT SMOKE DETECTORS OK
4) CAPTURE AND CONTAINMENT OK
5) OK FOR FINAL
01/14/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A PARTITION BETWEEN DEEP FAT FRYER AND STOVE. SEE FIRE INSPECTOR FOR DETAILS
2) PROGRAM T-STAT FOR FAN TO RUN DURING OCCUPIED HOURS
3) NEED TO SEE BATHROOM EXHAUST CONNECTED TO A/C FAN
4) SPARY PAINT NOT ADEQUATE PROTECTION FOR EXPOSED LINE SET INSULATION
5) PROVIDE RESTRAINTS ON HINGES FOR EXHAUST FANS
6) HEAT SENSOR TEST OK
7) NEED CAPTURE, CONTAINMENT AND AIR BALANCE REPORT
01/05/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PAINT EXPOSED ARMAFLEX WITH A PROTECTIVE COATING
2) SECURE CONDENSOR ON ROOF
3) PERMANENTLY I.D. ALL EQUIPMENT ON ROOF
4) NEED CAPTURE AND COTAINMENT TEST, HEAT SENSOR TEST AND AIR BALANCE REPORT
5) OK FOR GAS CLEARANCE