Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01302
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2011 | ELECTRIC - FINAL | Approved | ||
02/02/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY CONTRACTOR CANCELLED |
|
01/20/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LAST ITEM IS INFORMATIONAL FOR CONTROL PANEL |
|
01/19/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/18/2011 | ELECTRIC - FINAL | Cancelled | CANCELLED PER SUPER TONY #631-9294 | |
01/18/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/14/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONTACTORS TO BE LISTED-NOT RECOGNIZED COMPONENT 2) SEAL ENTRANCES TO WALK IN BOXES PER 300.7 3) PLEASE VERIFY LISTING FOR BUNN COFFEE MACHINE 4) BOXES MORE THAN 1/4" OR 1/8" PER 314.20 + 21 5) PROPERLY SUPPORT M/C CABLE FRONT DOOR 6) ALL KITCHEN, PREP AND DISHWASHING AREA RECEPTS TO BE PER 210.8 (B) 7) EM/EXIT FRONT DOOR NOT WORKING 8) WHERE IS CONTROL PANEL PER PLANS ? 9) CHECK ROOF NEXT TIME |
|
01/05/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FINISH WORK ON PATIO AND INSIDE 2) BAD EM LIGHT 3) DISCONNECT FOR FAN COIL UNIT 4) SERVICE RECEPTS FOR A/C AND RETRY EQUIPMENT WITHIN 25' 5) LABELING AND PANEL SCHEDULES 6) BAD GFI RECEPT |