Permit: T10CM01302

Parcel: 12810082B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM01302

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2011 ELECTRIC - FINAL Approved
02/02/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NOT READY CONTRACTOR CANCELLED
01/20/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LAST ITEM IS INFORMATIONAL FOR CONTROL PANEL
01/19/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/18/2011 ELECTRIC - FINAL Cancelled CANCELLED PER SUPER TONY #631-9294
01/18/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/14/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTACTORS TO BE LISTED-NOT RECOGNIZED COMPONENT
2) SEAL ENTRANCES TO WALK IN BOXES PER 300.7
3) PLEASE VERIFY LISTING FOR BUNN COFFEE MACHINE
4) BOXES MORE THAN 1/4" OR 1/8" PER 314.20 + 21
5) PROPERLY SUPPORT M/C CABLE FRONT DOOR
6) ALL KITCHEN, PREP AND DISHWASHING AREA RECEPTS TO BE PER 210.8 (B)
7) EM/EXIT FRONT DOOR NOT WORKING
8) WHERE IS CONTROL PANEL PER PLANS ?
9) CHECK ROOF NEXT TIME
01/05/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) FINISH WORK ON PATIO AND INSIDE
2) BAD EM LIGHT
3) DISCONNECT FOR FAN COIL UNIT
4) SERVICE RECEPTS FOR A/C AND RETRY EQUIPMENT WITHIN 25'
5) LABELING AND PANEL SCHEDULES
6) BAD GFI RECEPT