Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/27/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH BONDING OF NIPPLES 2) FINISH SECURING CONDUCTORS 3) NEED CUT SHEETS FOR MODULE MOUNTING INSTRUCTIONS |
|
| 05/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS/PERMIT ON SITE 2) TIGHTEN LOOSE FITTINGS 3) BONDING FOR GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 AND 250.92 4) NEED METER SOCKET PULLED AND D/C DISCONNECT OPENED 5) ROOF: PROVIDE PHYSICAL PROTECTION FOR CONDUCTORS 6) PLEASE VERIFY PERMIT FOR A/C INSTALLATION-RACEWAYS NOT INSTALLED TO CODE |