Permit: T10CM01300

Parcel: 116010600

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/04/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/27/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH BONDING OF NIPPLES
2) FINISH SECURING CONDUCTORS
3) NEED CUT SHEETS FOR MODULE MOUNTING INSTRUCTIONS
05/26/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS/PERMIT ON SITE
2) TIGHTEN LOOSE FITTINGS
3) BONDING FOR GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 AND 250.92
4) NEED METER SOCKET PULLED AND D/C DISCONNECT OPENED
5) ROOF: PROVIDE PHYSICAL PROTECTION FOR CONDUCTORS
6) PLEASE VERIFY PERMIT FOR A/C INSTALLATION-RACEWAYS NOT INSTALLED TO CODE