Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T10CM01276
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) FOR FINALS ONLY |
|
06/25/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
06/08/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FRONT STAIR NOT TO CODE 2) GFCI IN 2ND FLOOR BATHROOM, (LIGHT TO REMAIN ON WHEN TRIPPED) 3) CLEAN UP SUB-PANEL, CAN'T HANDLE 60/60 FEED TO OUT BLDG MAIN SERVICE IS ONLY 100 AMP, ALL BREAKERS TO BE GE TYPE 4) BEDROOM EGRESS WINDOWS NEED MIN. 5.6 SQUARE FT 5) COMBUSTION AIR 3,000 BTU 1 SQ. INCH=OF TOTAL BTU 6) ONE HOT WIRE AND ONE NEUTRAL PER CONNECTION 7) SMOKE DETECTORS REQUIRED IN BEDROOMS 8) REMOVE LOFT STAIR, ADD GUARDRAILING 30" HIGH 9) REAR SHEDS NOT TO DRAIN ON NEIGHBORS PROPERTY 10) SUPPLY LEDGER, LETTER HEAD FROM LICENSED CONTRACTOR PLUMBING, MECHANICAL AND ELECTRICAL 11) REAR PORCH ADD HANGER TO BACK SIDE OF FACIA |
|
05/24/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |