Permit: T10CM01276

Parcel: 107082080

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T10CM01276

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2010 BUILDING - FINAL Approved IVRS - Inspection :*
1) FOR FINALS ONLY
06/25/2010 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
06/08/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT STAIR NOT TO CODE
2) GFCI IN 2ND FLOOR BATHROOM, (LIGHT TO REMAIN ON WHEN TRIPPED)
3) CLEAN UP SUB-PANEL, CAN'T HANDLE 60/60 FEED TO OUT BLDG MAIN SERVICE IS ONLY 100 AMP, ALL BREAKERS TO BE GE TYPE
4) BEDROOM EGRESS WINDOWS NEED MIN. 5.6 SQUARE FT
5) COMBUSTION AIR 3,000 BTU 1 SQ. INCH=OF TOTAL BTU
6) ONE HOT WIRE AND ONE NEUTRAL PER CONNECTION
7) SMOKE DETECTORS REQUIRED IN BEDROOMS
8) REMOVE LOFT STAIR, ADD GUARDRAILING 30" HIGH
9) REAR SHEDS NOT TO DRAIN ON NEIGHBORS PROPERTY
10) SUPPLY LEDGER, LETTER HEAD FROM LICENSED CONTRACTOR PLUMBING, MECHANICAL AND ELECTRICAL
11) REAR PORCH ADD HANGER TO BACK SIDE OF FACIA
05/24/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*