Permit: T10CM01273

Parcel: 135042590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/14/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/11/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE CONDUCTOR IN THE ELECTRIC DISCONNECT LINE AND LOAD ARE SWITCHED
2) DO NOT USE WHITE WIRE
3) PROVIDE A BUSHING IN THE DISCONNECT
4) PROVIDE A COVER PLATE ON SLB ON ROOF
5) DO NOT USE INDOOR FITTINGS ON EMT
6) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS
7) PAINT EXPOSED PVC WITH LATEX PAINT
8) BLOCK AND CLAMP PVC
9) SECURE PVC TO THE WALL
10) TERMINATE WITH AN ELBOW AND NIPPLE
11) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF WITH A BUBBLE TYPE COVER
12) 50 AMP BREAKER TO LARGE, 45 IS MAX
13) PROVIDE R8 DUCT LINER IN EXPOSED DUCT ON ROOF