Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE CONDUCTOR IN THE ELECTRIC DISCONNECT LINE AND LOAD ARE SWITCHED 2) DO NOT USE WHITE WIRE 3) PROVIDE A BUSHING IN THE DISCONNECT 4) PROVIDE A COVER PLATE ON SLB ON ROOF 5) DO NOT USE INDOOR FITTINGS ON EMT 6) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS 7) PAINT EXPOSED PVC WITH LATEX PAINT 8) BLOCK AND CLAMP PVC 9) SECURE PVC TO THE WALL 10) TERMINATE WITH AN ELBOW AND NIPPLE 11) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF WITH A BUBBLE TYPE COVER 12) 50 AMP BREAKER TO LARGE, 45 IS MAX 13) PROVIDE R8 DUCT LINER IN EXPOSED DUCT ON ROOF |