Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66 #8 MIN. 2) GROUND PV UNITS PER PLAN AND NEC 3) LADDER TO SHORT-MUST HAVE 3 RINGS ABOVE PARAPET PER OSAB |
|
| 06/02/2010 | ELECTRIC - FINAL | Cancelled | CANCELLED PER CONTRACTOR SHAWN #631-7684 |