Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM01251

Parcel: 11706315E


Addresses:

450 S TOOLE AV


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T10CM01251

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2011 ELECTRIC - TEMP POWER FOR TEST Approved
12/15/2010 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
11/23/2010 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
11/22/2010 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) BOND RISER AT CT CAN 250.92
2) NEED REJECTION PINS
3) SEPERATE GROUNDS AND NEUTRALS PAST MAIN DISCONNECT 250.24
4) FILL UNUSED OPENINGS AND PORTIONS OF RACEWAYS IN MAIN PANELS
5) IGNITABLE MATERIAL IN BOTTOM OF SWITCH BOARD 408.17