Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2011 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
| 12/15/2010 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 11/23/2010 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
| 11/22/2010 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) BOND RISER AT CT CAN 250.92 2) NEED REJECTION PINS 3) SEPERATE GROUNDS AND NEUTRALS PAST MAIN DISCONNECT 250.24 4) FILL UNUSED OPENINGS AND PORTIONS OF RACEWAYS IN MAIN PANELS 5) IGNITABLE MATERIAL IN BOTTOM OF SWITCH BOARD 408.17 |