Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10CM01245

Parcel: 111050770

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/02/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/30/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CLOSET FLANGES ARE TO BE SCREWED OR SECURED IN AN APPROVED MANNER
12/13/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER WALLS
2) NEED TO SEE CLOSET FLANGES
12/12/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ABS HAS BEEN MODIFIED-RETEST THRU ROOF
2) REQUIRE 18" OF COPPER PRIOR TO VALVES ON A PEX SYSTEM. IE...WATER SERVICE CONNECTION, WATER HEATER VALVE AND HOSE BIBBS, ETC.....
12/09/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/07/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) POINT OF VENT MAY NOT BE BELOW THE TRAP WEIR
2) SUPPORT HORIZONTAL PIPING OVER HEAD
3) EXTEND 1" CN TO 1ST TEE
12/07/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE APPROVED PLAN CHANGES TO WATER
2) A ? CUT SHEET FOR EWC AND HAND SINK
11/30/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) REVISE PLAN TO SHOW NEW 1" SERVICE
2) WATER DISTRIBUTION NOT PER PLAN, NO RED LINES ON SITE, WATER SHOW AS EXISTING HAS BEEN REPLACED
3) PLUMBERS TAPE NOT APPROVED STRAP
4) ABS WATER TEST OK
5) ? STRAPS FOR STUBOUTS 2 HOLE STRAPS FOR SUPPORT-ISOLATORS FOR HOLES
11/23/2011 PLUMBING - INTERMEDIATE Not ready for Inspection 1. PLAN DOES NOT SHOW NEW 1" CW SERVICE FROM METER TO BUILDING, REVISE PLAN, OK TO COVER SUBJECT TO REVISED PLAN. IS A RPPBP REQUIRED?
2. NO TEST ON ABS, SUPPORT VERTICAL PIPING, FHA STRAPS ON NAIL GUARDS.
3. PLAN CALLS FOR COPPER WATER PIPING, CLEAN-OUTS IN CONCRETE TO BE LOWERED AND FP CO COVER INSTALLED
09/29/2011 PLUMBING - INTERMEDIATE Partial Approval