Permit: T10CM01245

Parcel: 111050770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/30/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) MAINTAIN WORKING SPACE IN FRONT OF SERVICE
2) DEVICES MORE THAN 1/4" 314.20 OR 1/8" 314.21 NEED AN APPROVED ARC SHIELD
3) WATER HEATER NOT A CORD CONNECTED APPLIANCE
4) EXIT SIGNS NOT WORKING
5) NEED PLAN REVISIONS FOR SERVICE
ROOF:
1) CORRECTLY IDENTIFY UN-GROUNDED CONDUCTORS
2) TIGHTEN LOOSE FITTINGS