Permit: T10CM01244

Parcel: 11707270A


Addresses:

555 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/28/2010 ELECTRIC - FINAL Approved
07/20/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HANDY BOXES OVERFILLED
2. PROPERLY SUPPORT M/C CABLE
3. EXIT LIGHTS NEED BOX AND OR PROPER FITTING PER INSTRUCTIONS
4. EAST EXIT NOT WORKING
5. ELECTRIC PLANS NOT AS INSTALLED ON SITE PLEASE REVISE
6. REVISE & INSTALL PANEL DIRECTOR PER 408.4