Permit: T10CM01237

Parcel: 11105076B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01237

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/27/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FAN COIL STILL OVER FUSED ACCORDING TO DATA PLATE MARKING
2) THE LINE SET TAPE USED IS NOT LISTED TAPE AND DOES NOT LAST IN SUNLIGHT
03/20/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) FAN COIL AND CONDENSOR DISCONNECTS OVER FUSED, 20 AMP IS MAX FOR BOTH DISCONNECTS
2) PROVIDE AN APPROVED PROTECTIVE COATING ON EXPOSED ARMAFLEX
3) INSTALL A 90 DEGREE ELBOW AT CONDENSATE TERMINATION
4) MARK FAN COIL DATA PLATE WITH PROPER HEAT STRIP INSTALLED
5) AIR BALANCE OK