Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM01237
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
03/27/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FAN COIL STILL OVER FUSED ACCORDING TO DATA PLATE MARKING 2) THE LINE SET TAPE USED IS NOT LISTED TAPE AND DOES NOT LAST IN SUNLIGHT |
|
03/20/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) FAN COIL AND CONDENSOR DISCONNECTS OVER FUSED, 20 AMP IS MAX FOR BOTH DISCONNECTS 2) PROVIDE AN APPROVED PROTECTIVE COATING ON EXPOSED ARMAFLEX 3) INSTALL A 90 DEGREE ELBOW AT CONDENSATE TERMINATION 4) MARK FAN COIL DATA PLATE WITH PROPER HEAT STRIP INSTALLED 5) AIR BALANCE OK |