Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T10CM01219
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2010 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/01/2010 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CITY APPROVED STAMP ON FIREWALL DETAIL 2) NOTES 4 & 5 FROM PREVIOUS 3) OK TO SHEETROCK |
|
| 08/12/2010 | FRAMING | Denied | IVRS - Inspection : 1. GROUND METAL BOXES 2. SECURE ALL U-GANG BOXES 3. NAIL PROTECT HOME RUNS 4. FIRE SEPARATION REQUIRED BETWEEN UNITS @ BEDROOM 2 & EXISTING SUBMIT FIRE WALL DETAIL 5. BEDROOM 3 WINDOW SIZE DOES NOT MEET EGRESS OPENING MINIMUM WIDTH OF 20" OPENING. 6. PROVIDE SIGNED APPEAL FOR WATER HEATER T&P DISCHARGE LINE TO PAN |
|
| 08/10/2010 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NEED INTERMEDIATE TRADES |
|
| 07/01/2010 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) TRADE INTERMEDIATES TO BE COMPLETE |