Permit: T10CM01207

Parcel: 117071470


Addresses:

610 S 4TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01207

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2010 ELECTRIC - INTERMEDIATE Approved
08/04/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/27/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED BRACKET BOXES 314.23
2) NEED M/C STRAPS AND SUPPORT WITHIN 12" 330.17
3) WIRE TO EXTEND 6" OUTSIDE OF BOX 300.14
4) USE APPROVED MOUNTING HARDWARE-NOT DRY WALL SCREWS
5) PROTECT M/C CABLE LESS THAN 1 1/4 306.4
6) UNDERGROUND TO BE PER 300.5
7) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
8) CONDUCTOR COLORS (210.5 AMENDMENTS) BL,RED AND BLUE
9) NEED ELECTRIC PLAN-FLOOR PLAN-AND NEW PANEL ONE LINE WITH LOAD CALCULATIONS
10) ONLY ONE CONDUCTOR PER TERMINAL LUG
11) NEED 2ND SCREW TO SECURE GROUND BAR AND CLEAN SURFACE 250.12