Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2010 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/04/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/27/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED BRACKET BOXES 314.23 2) NEED M/C STRAPS AND SUPPORT WITHIN 12" 330.17 3) WIRE TO EXTEND 6" OUTSIDE OF BOX 300.14 4) USE APPROVED MOUNTING HARDWARE-NOT DRY WALL SCREWS 5) PROTECT M/C CABLE LESS THAN 1 1/4 306.4 6) UNDERGROUND TO BE PER 300.5 7) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 8) CONDUCTOR COLORS (210.5 AMENDMENTS) BL,RED AND BLUE 9) NEED ELECTRIC PLAN-FLOOR PLAN-AND NEW PANEL ONE LINE WITH LOAD CALCULATIONS 10) ONLY ONE CONDUCTOR PER TERMINAL LUG 11) NEED 2ND SCREW TO SECURE GROUND BAR AND CLEAN SURFACE 250.12 |