Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T10CM01207
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2010 | FRAMING | Approved | IVRS - Inspection :* | |
07/13/2010 | FRAMING | Partial Approval | IVRS - Inspection :* 1) REVISE PLAN FOR CORRECT SET BACK 4' NOT 6' 2) TRUSS CALCS NEED TO BE APPROVED BY CITY 3) PLAN CALLS FOR 2 X 6 HEADERS 4) ANCHOR BOLTS WITHIN 12" FROM THE ENDS OF PLATE 5) MISSING SIMPSON CLIPS AND PER PLAN 10 LH20B, REVISE OR INSTALL |