Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MIN R8 DUCT LINER IN ALL EXPOSED DUCT ON THE ROOF 2) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND. PAINT ALL EXPOSED PVC WITH LATEX PAINT. USE PURPLE PRIMER ON ALL GLUED FITTINGS PRIOR TO GLUE. SUPPORT PVC EVERY 4' 3) SUPPORT THE ELECTRIC CONDUIT TO THE A/C UNIT 4) DO NOT USE WHITE WIRE FOR POWER TO A/C UNIT 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF |