Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) PLEASE RESCHEDULE WHEN SOMEONE WILL BE HOME |
|
| 11/17/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) BLOCK AND CLAMP CONDENSATE PIPE EVERY 4' AND SECURE TO WALL 2) PROVIDE A BUSHING IN ELECTRIC DISCONNECT |
|
| 10/29/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/04/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT GAS LINE ON ROOF 2) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAIN. BLOCK AND CLAMP EVERY 4'. TERMINATE TO WITHIN 6" OF THE GROUND 3) SUPPORT ELECTRIC CONDUIT. PROVIDE A BUSHING IN THE ELECTRIC DISCONNECT 4) 3/8" I.D. X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU 5) 1/2" GAS PIPE NOT ADEQUATE FOR 100,000 BTU MORE THAN 20' FROM METER. USE 3/4" FROM PIPE AT OUTSIDE OF HOUSE |