Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
Permit Number - T10CM01178
Inspection Description - BUILDING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2010 | BUILDING - PROGRESS | Approved | IVRS - Inspection :* | |
07/21/2010 | BUILDING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
05/24/2010 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REAR PANEL NOT TO CODE, MAIN DISCONNECT REQUIRED AT 6 CIRCUITS. SPLICE OF MAIN FEEDERS AND PULL PERMIT FOR REPAIR 2) GAS LINE UNDER REAR PORCH REROUTE 3) 8' CLEARANCE NEEDED AT MAIN DROP AND REAR PORCH 4) GFCI PROTECT STORAGE OUTLET AND TESTS OPEN GROUND 5) EXPOSE BREAK THRU. LINTEL ATTACHMENT AND BEAM TO LINTEL 6) PROVIDE LETTER HEAD LICENSED ELECTRICIAN STATING ALL WORK TO CODE OR EXPOSE ALL ELECTRICAL |
|
05/11/2010 | BUILDING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE LEAVE PLAN AND PERMIT ON SITE. PLAN TO SHOW FRONT/REAR PORCHES/GAS, IRON PIPE H20 LINE UNDERSLAB 2) LOCATE 2ND SUB PANEL, WAS SERVICE UPGRADE PERMIT OBTAINED ? LIGHTING CIRCUIT POWER SOURCE 3) HEATING REQUIRED FOR NEW ROOM 50/0 OF DIVIDING WALL NOT OPEN 4) HEADER FOR BOTH BEAMS INSTALL, WHAT TYPE/SIZE BEARING ? 5) SMOKE DETECTORS REQUIRED 6) MISSING RECEPT AT WEST SIDE OF OPENING TO NEW ROOM |