Permit: T10CM01169

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - PRE SLAB

Permit Number - T10CM01169

Inspection Description - PLUMBING - PRE SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2010 PLUMBING - PRE SLAB Approved IVRS - Inspection :*
1) OK FOR CONCRETE
07/23/2010 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
07/22/2010 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
07/21/2010 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
1) 3" TRAP ARM MAY NOT EXCEED 6' FROM TRAP WEIR TO POINT OF VENT
2) TRAP ARM TO BE INSTALLED AT 1/4" PER FEET
07/16/2010 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) N/H DWV UNDERFLOOR SANITARY SEWER OK TO COVER
2) GREASE WASTE TO 3 COMP SINK OK TO COVER
3) NEED TO SEE FLOOR SINKS AND TRENCH DRAINS
07/15/2010 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*