Permit: T10CM01163

Parcel: 10511061R

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM01163

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/24/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE SEISMIC RESTRAINTS ON ALL GRILLS AND REGISTERS IN T-BAR CEILINGS
2) OK FOR TILES EXCEPT TO VERIFY ITEM 1
3) PROVIDE 2" BEADED COLLARS AT ALL FLEX CONNECTIONS
08/10/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO PROCEED