Permit: T10CM01138

Parcel: 13613001T

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM01138

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) FOR FINAL PROVIDE APPROVED MECHANICAL PLAN, PERMITS FOR 2 A/C UNITS INSTALLED WITHOUT PERMITS OR INSPECTIONS
2) UNITS ARE MISSING FRESH AIR INTAKES, WRONG FUSES, WRONG DISCONNECT, CONDENSATE NOT PROPERLY SUPPORTED OR PAINTED WITH LATEX PAINT, IMPROPER WRING METHODS, CANVAS CONNECTOR NOT PROPERLY COVERED, I.D. DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY
05/26/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A MECHANICAL PLAN SHOWING THE NEW DUCT SYSTEM, OUTSIDE AIR REQUIREMENTS, EXHAUST HOOD, AIR BALANCING QUANTITIES, ETC...
2) NEED TO SEE PANDUIT STRAPS ON ALL FLEX DUCTING
3) PROVIDE SUPPORT FOR ALL DIFFUSERS