Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM01138
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) FOR FINAL PROVIDE APPROVED MECHANICAL PLAN, PERMITS FOR 2 A/C UNITS INSTALLED WITHOUT PERMITS OR INSPECTIONS 2) UNITS ARE MISSING FRESH AIR INTAKES, WRONG FUSES, WRONG DISCONNECT, CONDENSATE NOT PROPERLY SUPPORTED OR PAINTED WITH LATEX PAINT, IMPROPER WRING METHODS, CANVAS CONNECTOR NOT PROPERLY COVERED, I.D. DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY |
|
05/26/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A MECHANICAL PLAN SHOWING THE NEW DUCT SYSTEM, OUTSIDE AIR REQUIREMENTS, EXHAUST HOOD, AIR BALANCING QUANTITIES, ETC... 2) NEED TO SEE PANDUIT STRAPS ON ALL FLEX DUCTING 3) PROVIDE SUPPORT FOR ALL DIFFUSERS |