Permit: T10CM01138

Parcel: 13613001T

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T10CM01138

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/26/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL OPEN KNOCKOUTS IN JUNCTION BOXES
2) ALL LIGHT FIXTURES NEED SIESMIC WIRE THIS INCLUDES PENDANT FIXTURES AND EXITS
3) STRAP MC CABLE TO WITHIN 12" OF CONNECTIONS IF NOT 6' FIXTURE WHIPS