Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/26/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL OPEN KNOCKOUTS IN JUNCTION BOXES 2) ALL LIGHT FIXTURES NEED SIESMIC WIRE THIS INCLUDES PENDANT FIXTURES AND EXITS 3) STRAP MC CABLE TO WITHIN 12" OF CONNECTIONS IF NOT 6' FIXTURE WHIPS |