Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 04/30/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDUIT (FLEX) TO BE BLOCKED UP OFF OF ROOF 2) BLOCKING ON 3/4" PVC NOT TO EXCEED 4' 3) CONDENSATE PIPING NOT PROPERLY COATED (IF I CAN READ THE PRINT ON THE PIPE IT'S NOT PROPERLY COATED) 4) P-TRAP IS INSTALLED BACKWARDS (INLET IS LOWER THAN OUTLET) 5) GROUND WIRE TO UNIT NOT PROPERLY IDENTIFIED 6) ALL PVC JOINTS AND FITTINGS ARE TO B PRIMED, PRIMER TO BE PURPLE IN COLOR (BLUE PVC GLUE IS NOT A SUBSTITUTE FOR PRIMER) 7) ROOF TOP DUCT IS NOT PROPERLY SUPPORTED |