Permit: T10CM01131

Parcel: 133353130


Addresses:

8942 E ANNA PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/04/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
04/30/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDUIT (FLEX) TO BE BLOCKED UP OFF OF ROOF
2) BLOCKING ON 3/4" PVC NOT TO EXCEED 4'
3) CONDENSATE PIPING NOT PROPERLY COATED (IF I CAN READ THE PRINT ON THE PIPE IT'S NOT PROPERLY COATED)
4) P-TRAP IS INSTALLED BACKWARDS (INLET IS LOWER THAN OUTLET)
5) GROUND WIRE TO UNIT NOT PROPERLY IDENTIFIED
6) ALL PVC JOINTS AND FITTINGS ARE TO B PRIMED, PRIMER TO BE PURPLE IN COLOR (BLUE PVC GLUE IS NOT A SUBSTITUTE FOR PRIMER)
7) ROOF TOP DUCT IS NOT PROPERLY SUPPORTED